Chapter 7 · Alternating Current

7.7 Power in an AC Circuit: The Power Factor

A voltage v = vₘ sin ωt applied to a series LCR circuit drives a current i = iₘ sin(ωt + φ), with iₘ = vₘ/⁠Z and the phase angle φ of Eq. (7.27). The power delivered by the source at each instant is

A product of two sines can be written as a difference of two cosines:

With A = ωt and B = ωt + φ, this gives

(7.29)

The first term in the bracket is constant. The second swings at twice the source frequency and averages to zero over a cycle. So the average power is

(7.30)

Using V = IZ and, from the impedance diagram (Fig. 7.15), cos φ = R/⁠Z, this can also be written as

The average power depends not only on the rms voltage and current but also on cos φ, which is called the . And however the reactances are arranged, all the power is used up in the resistance.

Phase angle (degrees)

30°

0

30

45

60

90

Fig. 7.18 Change the phase angle between v and i. The power p = vi (green) is positive and negative in turn; its average, the dashed line, falls from vₘiₘ/⁠2 at φ = 0 to zero at φ = 90°.

Fig. 7.18 shows how the phase angle shapes the power. Four cases stand out:

A purely resistive circuit: φ = 0, the power factor is 1, and the power is the largest it can be for the given voltage and current. A purely inductive or purely capacitive circuit: φ = ±π/⁠2 and the power factor is 0. A current flows, but on average no power is used. Such a current is called a . An LCR, RL or RC circuit: φ lies in between, and the power is used up only in the resistor. An LCR circuit at resonance: the reactances cancel, φ = 0 and cos φ = 1, so P = I²R. For a given resistance, the circuit draws the most power at resonance.

The power factor matters a great deal in power distribution. Electric motors, fans and pumps contain large coils, so they draw a current that lags the voltage. Fig. 7.19 splits such a current into two parts: a part Iₚ in phase with the voltage, which carries the power, and a wattless part at right angles to it, which carries none. The wattless part still flows through every cable and transformer between the power station and the motor, and heats them. A capacitor joined in parallel with the motor draws a current that leads the voltage by π/⁠2. If it equals the wattless part, the two cancel, and the line carries only Iₚ.

Fig. 7.19 (a) A lagging current I splits into a power part along V and a wattless part at right angles to it. (b) A capacitor in parallel draws a leading current that cancels the wattless part, leaving only the power part in the line.

Example 7.12

Find the power factor and the average power for the circuit of Example 7.9. What is the average power at resonance (Example 7.10)?

Given

R = 80 Ω, Z = 100 Ω vₘ = 200 V, iₘ = 2.0 A At resonance: iₘ = 2.5 A

Solution

The power factor is R/⁠Z.

The average power, from Eq. (7.30):

Check it as I²R, with the rms current iₘ/⁠√2:

At resonance the power factor is 1 and the current is larger.

Answer

cos φ = 0.80, P = 160 W; 250 W at resonance

Example 7.13

An electric motor draws 5.0 A from a 230 V, 50 Hz line and uses 920 W. Find (a) its power factor, (b) the power part and the wattless part of its current, and (c) the capacitance that, joined in parallel with the motor, makes the line current as small as possible. By what fraction does this cut the heating of the line?

Given

V = 230 V, I = 5.0 A, ν = 50 Hz Average power P = 920 W; the current lags

Solution

(a) The power factor is the average power divided by VI.

(b) The power part is I cos φ and the wattless part is I sin φ, where

(c) The capacitor must draw a leading current of 3.0 A to cancel the wattless part. Its current is the voltage divided by its reactance, ωCV, so

Now the line carries only the power part, 4.0 A, while the motor runs exactly as before. Heating in the line goes as the square of the current:

Answer

cos φ = 0.80; 4.0 A and 3.0 A; 41.5 µF; 36 % less

Did you know?

Power factor and the electricity bill

Factories with many motors are usually charged extra if their power factor is low, because the wattless current loads the supply network without paying for energy. Banks of capacitors, switched in automatically, keep their power factor close to 1.

Check yourself

A 230 V supply drives an rms current of 2.0 A through an ideal inductor. What average power does the inductor take?

Check yourself

What is the power factor of a series LCR circuit at resonance?

Chapter 7 · Alternating Current

7.7 Power in an AC Circuit: The Power Factor

A voltage v = vₘ sin ωt applied to a series LCR circuit drives a current i = iₘ sin(ωt + φ), with iₘ = vₘ/⁠Z and the phase angle φ of Eq. (7.27). The power delivered by the source at each instant is

A product of two sines can be written as a difference of two cosines:

With A = ωt and B = ωt + φ, this gives

(7.29)

The first term in the bracket is constant. The second swings at twice the source frequency and averages to zero over a cycle. So the average power is

(7.30)

Using V = IZ and, from the impedance diagram (Fig. 7.15), cos φ = R/⁠Z, this can also be written as

The average power depends not only on the rms voltage and current but also on cos φ, which is called the . And however the reactances are arranged, all the power is used up in the resistance.

Phase angle (degrees)

30°

0

30

45

60

90

Fig. 7.18 Change the phase angle between v and i. The power p = vi (green) is positive and negative in turn; its average, the dashed line, falls from vₘiₘ/⁠2 at φ = 0 to zero at φ = 90°.

Fig. 7.18 shows how the phase angle shapes the power. Four cases stand out:

A purely resistive circuit: φ = 0, the power factor is 1, and the power is the largest it can be for the given voltage and current. A purely inductive or purely capacitive circuit: φ = ±π/⁠2 and the power factor is 0. A current flows, but on average no power is used. Such a current is called a . An LCR, RL or RC circuit: φ lies in between, and the power is used up only in the resistor. An LCR circuit at resonance: the reactances cancel, φ = 0 and cos φ = 1, so P = I²R. For a given resistance, the circuit draws the most power at resonance.

The power factor matters a great deal in power distribution. Electric motors, fans and pumps contain large coils, so they draw a current that lags the voltage. Fig. 7.19 splits such a current into two parts: a part Iₚ in phase with the voltage, which carries the power, and a wattless part at right angles to it, which carries none. The wattless part still flows through every cable and transformer between the power station and the motor, and heats them. A capacitor joined in parallel with the motor draws a current that leads the voltage by π/⁠2. If it equals the wattless part, the two cancel, and the line carries only Iₚ.

Fig. 7.19 (a) A lagging current I splits into a power part along V and a wattless part at right angles to it. (b) A capacitor in parallel draws a leading current that cancels the wattless part, leaving only the power part in the line.

Example 7.12

Find the power factor and the average power for the circuit of Example 7.9. What is the average power at resonance (Example 7.10)?

Given

R = 80 Ω, Z = 100 Ω vₘ = 200 V, iₘ = 2.0 A At resonance: iₘ = 2.5 A

Solution

The power factor is R/⁠Z.

The average power, from Eq. (7.30):

Check it as I²R, with the rms current iₘ/⁠√2:

At resonance the power factor is 1 and the current is larger.

Answer

cos φ = 0.80, P = 160 W; 250 W at resonance

Example 7.13

An electric motor draws 5.0 A from a 230 V, 50 Hz line and uses 920 W. Find (a) its power factor, (b) the power part and the wattless part of its current, and (c) the capacitance that, joined in parallel with the motor, makes the line current as small as possible. By what fraction does this cut the heating of the line?

Given

V = 230 V, I = 5.0 A, ν = 50 Hz Average power P = 920 W; the current lags

Solution

(a) The power factor is the average power divided by VI.

(b) The power part is I cos φ and the wattless part is I sin φ, where

(c) The capacitor must draw a leading current of 3.0 A to cancel the wattless part. Its current is the voltage divided by its reactance, ωCV, so

Now the line carries only the power part, 4.0 A, while the motor runs exactly as before. Heating in the line goes as the square of the current:

Answer

cos φ = 0.80; 4.0 A and 3.0 A; 41.5 µF; 36 % less

Did you know?

Power factor and the electricity bill

Factories with many motors are usually charged extra if their power factor is low, because the wattless current loads the supply network without paying for energy. Banks of capacitors, switched in automatically, keep their power factor close to 1.

Check yourself

A 230 V supply drives an rms current of 2.0 A through an ideal inductor. What average power does the inductor take?

Check yourself

What is the power factor of a series LCR circuit at resonance?